Van Mode: On-Site Quick Reference
High-contrast, tactile lookup tool designed for one-handed operation on mobile screens in direct sunlight. Pre-cached for full offline use in basements with zero mobile reception.
Saved for offline plant-room use
BS 7671:2018+A4:2026 · On-Site Guide Table A1BS 7671 Earth Fault Loop Impedance (Zs)
Select device and rating to see both the BS 7671 tabulated limit (Table 41.2 to 41.4) and the measured on-site limit with the mandatory 0.8 temperature correction multiplier applied.
Max Measured Zs (80%)1.10 ΩCompare against site test reading
Tabulated 100% Limit1.37 ΩTable 41.3 at conductor operating temp
Show Full Mathematical Derivation (AM2 Working Standard)BS 7671:2018+A4:2026
AM2 PORTFOLIO & DESIGN AUDIT FORMATTRANSPARENT FIRST-PRINCIPLES MATHS
Step 1 · Stated Test Limits
Maximum Allowable Measured Zs (80% Cold Rule)
Zs(test) ≤ 1.10 Ω (Operating Tabulated Limit: 1.37 Ω)
On-Site Guide Table B6 · BS 7671 Table 41.3
Step 2 · Regulation Formula
Earth Fault Loop Impedance (Reg 411.4.4)
Zs(tab) ≤ (U0 × Cmin) / Ia
U0 = 230 V, Cmin = 0.95 (BS 7671 Table 41.1)
Step 3 · Conductor Temperature Correction (80% Rule)
Cold Circuit Testing Adjustment
Zs(test) ≤ 0.8 × Zs(tab)
BS 7671 Appendix 3 · Rule of thumb for testing at ambient temperature
Statutory Compliance Note:Worked example to BS 7671:2018+A4:2026. To be verified by a competent person against current standards and manufacturer data before use (EAWR 1989).