Van Mode: On-Site Quick Reference

High-contrast, tactile lookup tool designed for one-handed operation on mobile screens in direct sunlight. Pre-cached for full offline use in basements with zero mobile reception.

Saved for offline plant-room use
BS 7671:2018+A4:2026 · On-Site Guide Table A1

BS 7671 Earth Fault Loop Impedance (Zs)

Select device and rating to see both the BS 7671 tabulated limit (Table 41.2 to 41.4) and the measured on-site limit with the mandatory 0.8 temperature correction multiplier applied.

Max Measured Zs (80%)1.10 ΩCompare against site test reading
Tabulated 100% Limit1.37 ΩTable 41.3 at conductor operating temp
Show Full Mathematical Derivation (AM2 Working Standard)
BS 7671:2018+A4:2026
AM2 PORTFOLIO & DESIGN AUDIT FORMATTRANSPARENT FIRST-PRINCIPLES MATHS
Step 1 · Stated Test Limits

Maximum Allowable Measured Zs (80% Cold Rule)

Zs(test) ≤ 1.10 Ω (Operating Tabulated Limit: 1.37 Ω)
On-Site Guide Table B6 · BS 7671 Table 41.3
Step 2 · Regulation Formula

Earth Fault Loop Impedance (Reg 411.4.4)

Zs(tab) ≤ (U0 × Cmin) / Ia
U0 = 230 V, Cmin = 0.95 (BS 7671 Table 41.1)
Step 3 · Conductor Temperature Correction (80% Rule)

Cold Circuit Testing Adjustment

Zs(test) ≤ 0.8 × Zs(tab)
BS 7671 Appendix 3 · Rule of thumb for testing at ambient temperature
Statutory Compliance Note:Worked example to BS 7671:2018+A4:2026. To be verified by a competent person against current standards and manufacturer data before use (EAWR 1989).
Formula & factors cross-checked against BS 7671:2018+A4:2026. Free of black-box approximations.