Max Zs Table & Calculator (BS 7671:2018+A4:2026)
Under BS 7671 Regulation 411.4.4, the earth fault loop impedance (Zs) must be low enough to ensure automatic disconnection of supply within the statutory time specified in Regulation 411.3.2. Because conductors are tested cold during on-site inspection, the 80% Rule (0.80 factor) per Appendix 3 and IET On-Site Guide Table B6 must be satisfied. This tool details every intermediate step, formula substitution, and regulatory margin.
Frequently Asked Questions
What is the maximum Zs for a 32A Type B MCB?
For a 230 V final circuit with 0.4 s disconnection, the trip current Ia is 160 A (5 × 32 A). With Cmin of 0.95, Table 41.3 gives a tabulated maximum Zs of 1.37 Ω. Applying the 80% rule from IET On-Site Guide Table B6 gives a measured test limit of 1.09 Ω.
What is the 80% rule for Zs testing?
Because conductors are tested cold on site, Appendix 3 and IET On-Site Guide Table B6 require the measured Zs to stay within 80% of the tabulated maximum for 70°C thermoplastic PVC cable. This guarantees automatic disconnection once conductors reach 70°C under fault conditions. For 90°C thermosetting XLPE, the factor is 0.78.
Why does a Type C MCB have a lower maximum Zs than a Type B?
A Type C breaker needs twice the fault current of a Type B to trip. For a 32 A device, Ia rises from 160 A to 320 A, roughly halving the 80% rule test limit from 1.09 Ω to 0.55 Ω. Moving from Type B to Type C makes fault loop compliance harder, not easier.