Back to Tools DirectoryThe 80% Rule (Zs) vs Tabulated Values Guide

Max Zs Table & Calculator (BS 7671:2018+A4:2026)

Under BS 7671 Regulation 411.4.4, the earth fault loop impedance (Zs) must be low enough to ensure automatic disconnection of supply within the statutory time specified in Regulation 411.3.2. Because conductors are tested cold during on-site inspection, the 80% Rule (0.80 factor) per Appendix 3 and IET On-Site Guide Table B6 must be satisfied. This tool details every intermediate step, formula substitution, and regulatory margin.

Plant-Room Ready: This calculator caches to your phone and works 100% offline with zero mobile signal. All calculations execute locally with sub-millisecond reactivity.
1-Click Quick Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Protective Device Specification
2. Measured On-Site Zs Reading (Optional)

Enter your actual measured loop test reading to evaluate statutory compliance and headroom:

Measured Test Zs (Ω)0.85 Ω
Tested cold with calibrated multifunction tester at 20°C ambient.

Loop Impedance Result

Standard Basis: BS 7671:2018+A4:2026 Table 41.3 · Cmin = 0.95Mode: 80% Test Rule (OSG Table B6)
Maximum Permitted Loop ImpedanceTable B6 · 80% Rule
1.09 Ω
Tabulated Max (70°C)1.37 Ω
Trip Current (Ia)160.0 A
Measured Test Zs0.85 Ω
ON-SITE COMPLIANCE VERDICT:WITHIN LIMIT

Measured 0.85 Ω is comfortably within statutory limit (1.09 Ω) with 22.0% headroom.

0.00 Ω (Direct Short)80% Limit: 1.09 ΩMax: 1.37 Ω
Why not Type C or next rating?

Why not Type C? A Type C 32A breaker requires 2× higher fault current (Ia = 320A), halving max allowed Zs to 0.55 Ω. Going B to C makes fault loop compliance harder, not easier.

Site Conditions & AdjustmentsStandard: 230V TN · 0.4s · Cmin 0.95 · 70°C PVC (0.80 Factor)
Nominal Supply Voltage (U0)
Reduced low voltage (RLV) circuits on building sites use 55V line-to-earth.
Voltage Factor (Cmin)Accounts for supply voltage variations down to -6% under minimum grid conditions.
Conductor Insulation ClassThermosetting 90°C XLPE cable has higher resistance rise under full design load.
Evaluation BasisThe 80% multiplier is the standard test gate during on-site initial verification.

Glass-Box AM2 Mathematical Derivation Pad

First Principles Verification · BS 7671 Reg 411.4.4
Regulatory ReferenceStandard FormulaActive SubstitutionCalculated Value
BS 7671 Reg 411.4.4Ia = Multiplier × In5 × 32 A160.0 A
BS 7671 Table 41.3Zs(tab) = (U0 × Cmin) ÷ Ia(230 V × 0.95) ÷ 160.0 A1.37 Ω
IET OSG Table B6Zs(test) = Zs(tab) × 0.801.37 Ω × 0.801.09 Ω
On-Site HeadroomHeadroom = Limit - Measured1.09 Ω - 0.85 Ω0.24 Ω (22.0%)

Frequently Asked Questions

What is the maximum Zs for a 32A Type B MCB?

For a 230 V final circuit with 0.4 s disconnection, the trip current Ia is 160 A (5 × 32 A). With Cmin of 0.95, Table 41.3 gives a tabulated maximum Zs of 1.37 Ω. Applying the 80% rule from IET On-Site Guide Table B6 gives a measured test limit of 1.09 Ω.

What is the 80% rule for Zs testing?

Because conductors are tested cold on site, Appendix 3 and IET On-Site Guide Table B6 require the measured Zs to stay within 80% of the tabulated maximum for 70°C thermoplastic PVC cable. This guarantees automatic disconnection once conductors reach 70°C under fault conditions. For 90°C thermosetting XLPE, the factor is 0.78.

Why does a Type C MCB have a lower maximum Zs than a Type B?

A Type C breaker needs twice the fault current of a Type B to trip. For a 32 A device, Ia rises from 160 A to 320 A, roughly halving the 80% rule test limit from 1.09 Ω to 0.55 Ω. Moving from Type B to Type C makes fault loop compliance harder, not easier.