Max Zs Table & Calculator (BS 7671:2018+A4:2026)

Under BS 7671 Regulation 411.4.4, the earth fault loop impedance (Zs) must be low enough to ensure automatic disconnection of supply within the statutory time specified in Regulation 411.3.2. Because conductors are tested cold during on-site inspection, the 80% Rule (0.8 factor) per Appendix 3 and On-Site Guide Table B6 must be satisfied. This tool details every intermediate step, formula substitution, and regulatory margin.

Plant-Room Ready: This calculator caches to your phone and works 100% offline with zero mobile signal. Add to your home screen for quick access on site.
1-Click Mobile Presets:Tap for instant on-site sizing
Select a preset above to auto-fill common circuit values
1. Protective Device Specification
Device Tripping Curve (1-Tap)
2. Disconnection & Supply
3. On-Site Measured Verification (Optional)

Loop Impedance Summary

⚡ UK ELECTRICAL WORKSTATIONCOMPLIANT
Circuit: Circuit C1
Max Permitted Zs (80% Rule): 1.10 Ω
Measured Test Reading: Awaiting test reading
Compliance Margin: Safe
Standard Basis: BS 7671 Table 41.3 · Cmin 0.95 included0.8 Factor: ON (10°C OSG/GN3 Cold Test)
Cold Test Maximum Measured Zs (80% Rule)BS 7671 Table 41.3 · OSG Table B6
-Ω
Operating Tabulated Limit (70°C): -Tripping Current (Ia): -

Why the 80% Rule is Mandatory for Testing: BS 7671 tabulated values are calculated for conductors at their maximum operating temperature (typically 70°C). When testing on cold, lightly-loaded circuits at ambient temperature (typically 10°C to 20°C), conductor resistance is lower. Multiplying tabulated Zs × 0.8 guarantees that when the circuit reaches full operating temperature under load, disconnection time will still be achieved.

Show Full Mathematical Derivation (AM2 Working Standard)
BS 7671:2018+A4:2026
AM2 PORTFOLIO & DESIGN AUDIT FORMATTRANSPARENT FIRST-PRINCIPLES MATHS
Step 1 · Stated Test Limits

Maximum Allowable Measured Zs (80% Cold Rule)

Zs(test) ≤ 1.10 Ω (Operating Tabulated Limit: 1.37 Ω)
On-Site Guide Table B6 · BS 7671 Table 41.3
Step 2 · BS 7671 formula & Voltage Factor

Earth Fault Loop Impedance (Reg 411.4.4)

Zs(tab) ≤ (U0 × Cmin) / Ia
Zs(tab) ≤ (230 × 0.95) / 160.0 = 218.5 / 160.0 = 1.365 Ω
  • U0 (Supply Voltage to Earth): 230 V (nominal single-phase voltage)
  • Cmin (Voltage Tolerance Factor): 0.95 (BS 7671 Table 41.1 minimum grid tolerance)
  • Ia (Tripping Operating Current): 160.0 A (instantaneous disconnection within 0.40 s)
Step 3 · Conductor Temperature Correction (80% Rule)

Cold Circuit Testing Adjustment

Zs(test) ≤ 0.8 × Zs(tab)
Zs(test) ≤ 0.8 × 1.365 = 1.092 Ω → 1.10 Ω
BS 7671 Appendix 3 · Conductor operating temperature (20°C to 70°C)
Statutory Compliance Note:Worked example to BS 7671:2018+A4:2026. To be verified by a competent person against current standards and manufacturer data before use (EAWR 1989).
Formula & factors cross-checked against BS 7671:2018+A4:2026. Free of black-box approximations.
Worked Example & Calculation Breakdown

Scenario: A 230 V single-phase ring final socket circuit is protected by a 32 A Type B MCB (BS EN 60898). An electrician carries out periodic testing (EICR) at an ambient temperature of 18°C and measures Zs = 0.92 Ω at the furthest socket.

  1. Determine Tripping Current: Type B MCB requires Ia = 5 × In = 5 × 32 = 160 A to guarantee disconnection within 0.4 seconds.
  2. Calculate Tabulated Maximum Zs: Zs(tab) = (230 × 0.95) / 160 A = 218.5 / 160 = 1.37 Ω (Cmin corrected) (per BS 7671 Table 41.3).
  3. Apply 80% Temperature Factor: Zs(max measured) = 1.37 × 0.80 = 1.10 Ω (per On-Site Guide Table B6).
  4. Compare Measured Reading: Zs(measured) = 0.92 Ω ≤ 1.10 Ω ⇒ PASS ✔. The circuit provides 0.18 Ω (16%) impedance safety headroom.

BS 7671 Regulatory Framework & Boundaries

⚠️ Engineering design aid: Always verify results against published BS 7671 tables and manufacturer specific breaker curves. Not a compliance certificate or legal sign-off.

Frequently Asked Questions

Why do measured on-site Zs values use the 80% (0.8) rule of thumb?

Tabulated Max Zs values in BS 7671 Chapter 41 are calculated for conductors at maximum operating temperature (typically 70°C for thermoplastic PVC). When testing cold circuits on site (~20°C), conductor resistance is lower. Multiplying tabulated Max Zs by 0.8 compensates for the temperature rise that will occur during an earth fault (BS 7671 Appendix 3).

What is the Cmin voltage factor in BS 7671?

BS 7671 incorporates a voltage factor Cmin = 0.95 into earth fault loop impedance calculations (230 V × 0.95 = 218.5 V). This ensures protective devices disconnect within disconnection time required by BS 7671s even when the UK national grid voltage drops to its minimum statutory tolerance.

What are the disconnection time required by BS 7671s under Regulation 411.3.2.2?

For standard 230V TN systems, final circuits not exceeding 63A with socket-outlets, and 32A for fixed equipment, require a maximum disconnection time of 0.4 seconds. For TT systems, the maximum time is 0.2 seconds. Distribution circuits allow up to 5.0 seconds (TN) or 1.0 second (TT).