Maximum Demand & Diversity Sizer
Assess maximum demand and circuit diversity for single-phase electrical installations under BS 7671:2018+A4:2026 Regulation 311.1 and IET On-Site Guide Appendix A (Table A1). Benchmarks calculated maximum demand against UK Distribution Network Operator (DNO) service head cut-out fuses (60 A, 80 A, 100 A), checks the 60 A continuous thermal stress limit (ENA EREC G12/4), and generates formatted text for electrical certification schedules.
Maximum Demand Assessment
Calculating headroom...
Circuit Breakdown (OSG Table A1)
| Load Group | Connected | Rule Applied | Demand |
|---|
Show Full Mathematical Derivation (AM2 Working Standard)BS 7671:2018+A4:2026
BS 7671 & IET On-Site Guide Diversity Principles
BS 7671:2018+A4:2026 Regulation 311.1 requires that for every design, the maximum demand of the installation shall be assessed. In domestic installations, diversity allows circuits to be sized for realistic simultaneous consumption rather than the arithmetic sum of connected loads. However, the rapid adoption of high-power continuous loads requires strict engineering vigilance:
1. Why Modern Electrified Loads Defeat Traditional Diversity
Traditional Table A1 diversity factors were developed when household loads were intermittent (kettles, toasters, cooking). Modern electrified loads break these assumptions:
- Electric Vehicle Supply Equipment (EVSE): Under Regulation 722.311, no diversity factor may be applied to an EV charging point unless Active Load Management (ALM) or Dynamic Load Balancing (DLB) to Regulation 722.311.201 is installed. A 7.4 kW charger draws a constant 32.17 A for 4 to 8 consecutive hours.
- Heat Pumps: Heat pump compressors run continuously for extended cycles during winter peak periods, coinciding with evening domestic lighting and cooking peaks. Auxiliary immersion heaters must be locked out by interlocks during compressor operation.
- ENA EREC G12/4 Continuous 60 A Threshold: Energy Networks Association (ENA) standard G12/4 notes that single-phase service heads subjected to continuous currents >60 A experience elevated thermal fatigue. Installations exceeding 60 A continuous draw require formal DNO notification.
2. Cooking Appliance Clamping Rule
Under IET OSG Table A1 item 2, household cooking appliances are calculated as:
Demand (A) = 10 A + 30% × (Iflc - 10 A) + 5 A (if control unit has socket)
This tool incorporates a safe mathematical clamp: if the appliance full load current is ≤ 10 A (e.g. a small plug-in induction hob), the demand is capped at Iflc to avoid artificially inflating a small load.
3. Instantaneous Water Heating & Shower Interlocks
Table A1 item 4 assesses multiple instantaneous water heaters at 100% of the largest unit, 100% of the second unit, and 25% of any remaining units. Two 9.5 kW showers running simultaneously draw 41.30 A + 41.30 A = 82.6 A, instantaneously overloading an 80 A cut-out fuse on their own. Installing a mechanical or contactor-based shower priority changeover switch interlocks the circuits so only one shower can run at once, cutting water heating demand by half.