DOL Motor Starter, Contactor & Overload Sizer

Precision sizing engine for three-phase Direct-On-Line (DOL) motor starters,AC-3 / AC-3e contactor selection, Class 10/20 thermal overload dial settings,BS 88-2 Type 2 coordination back-up fusing, BS 7671 feeder cable voltage drop, and BS EN 61439-2 Form 4 MCC panel segregation.

Motor & Supply Rating
Feeder Cable & Control Circuit

Starter Engineering Telemetry

Motor Full Load Current (FLC)-- A
Locked-Rotor Inrush Current-- A
Contactor Sizing (BS EN 60947-4-1)--
Thermal Overload Dial Setting--
Type 2 Back-up Fuse (BS 88-2 gM)--
Alternative SCPD (MPCB / Type D)--
Feeder Cable (BS 7671 XLPE/SWA)-- mm²
Volt Drop: Running / Starting-- % / -- %
Earth Fault Loop (Max Zs & Route Limit)--
Control Transformer VA (BS EN 60204-1)-- VA
BS EN 61439-2 Segregation Spec--

Standard DOL Wiring & Form 4 Compartment Reference

BS EN 60617 Standard Engineering Symbols • BS EN 61439-2 Physical Segregation Boundaries

FORM 4: BUSBAR CHAMBERFORM 4: FUNCTIONAL UNIT COMPARTMENT (Q1, F0, KM1, F1)FORM 4b: SEPARATE CABLE TERMINATION CHAMBER3-PHASE 400V POWER CIRCUITCONTROL CIRCUIT (BS EN 60204-1)L1L2L3Q1 IsolatorF0 (BS 88)KM1 (AC-3e)F1 OverloadM3~+24V DC / Control Line0V DC / NeutralFC (2A)S0 E-Stop (NC)S1 Stop (NC)S2 StartKM1 (13-14)F1 95-96 (NC)KM1F1 97-98 (NO)H1
Show Full Mathematical Derivation (AM2 Working Standard)
BS 7671:2018+A4:2026
AM2 PORTFOLIO & DESIGN AUDIT FORMATTRANSPARENT FIRST-PRINCIPLES MATHS

Engineering Design Guidance: BS EN IEC 60947-4-1:2019 & BS EN 61439-2

1. AC-3 vs AC-3e Contactor Utilisation

Standard AC-3 covers typical squirrel-cage motors (starting and switching off during running). However, under UK Eco-Design statutory mandates (SI 2021/1095), motors from 0.75 kW to 1000 kW must meet IE3 (Premium) or IE4 (Super Premium) efficiency. These motors feature higher copper slot fill and lower rotor resistance, resulting in locked-rotor starting inrush currents reaching 7.5× to 8.5× FLC (compared to 6× for legacy IE1 motors). Always verify contactor compliance with AC-3e (introduced in BS EN IEC 60947-4-1:2019) to prevent premature contact erosion and dynamic contact welding during cold starts.

2. BS EN IEC 60947-4-1:2019 Type 2 Coordination

Type 2 Coordination requires that under a short-circuit fault, the starter and contactor cause no hazard to operators or surrounding plant and remain fully functional without replacement of components (light contact tacking is permissible if easily freed with a screwdriver without significant deformation). To achieve Type 2 coordination:

  • BS 88-2 gM Fuses: Dual-rated motor fuses (e.g. 32M50) provide a continuous 32A thermal rating with a 50A melting time-current curve to absorb starting inrush without nuisance aging.
  • Partial-range aM Fuses: Provide high-speed short-circuit protection only; the thermal overload relay F1 handles all overload currents.
  • Motor Protection Circuit Breakers (MPCB): Combined units offering instantaneous magnetic tripping (12 to 14× FLC) and temperature-compensated thermal protection.

3. BS EN 61439-2 Forms of Internal Separation

In industrial Motor Control Centres (MCCs), internal barriers mitigate risk to personnel during inspection or maintenance. The primary forms of separation for starter cubicles are:

FormBusbarsFunctional StartersExternal TerminalsTypical UK Sector
Form 2bSeparated from startersNot separated from each otherSeparated from busbars (common chamber)Light commercial & HVAC
Form 3bSeparated from startersSeparated from each otherSeparated from busbars (common chamber)BMS plantrooms & institutional
Form 4b Type 6Separated by metallic barriersSeparated in individual cubiclesSeparated in dedicated individual terminal boxesStandard UK industrial MCC / Factories
Form 4b Type 7Fully segregated busbar chamberWithdrawable or fixed cubiclesIndividual terminal boxes with dedicated glanding platesWIMES 3.01 (Water) & HTM 06-01 (Health)

4. Feeder Cable & Voltage Drop Sizing (BS 7671)

Motor feeders must satisfy Regulation 433.1 (Ib ≤ In ≤ Iz) under continuous running, and limit transient starting voltage drop to < 8%. A starting voltage drop exceeding 10% can cause contactor coil chattering, thyristor misfiring, or extended run-up times triggering premature thermal overload trips.

Formula & factors cross-checked against BS 7671:2018+A4:2026. Free of black-box approximations.
Industrial Machinery Compliance Note:Worked example to BS EN 60204-1 (§5.3 isolation, §9.2.2 Stop Categories), BS EN IEC 60947-4-1:2019 (AC-3 contactor rating), and PUWER 1998 Regulation 19. All motor starter configurations must be verified by a competent engineer before installation (EAWR 1989).