Generator Sizing Calculator
Most generator calculators add up your running load and stop there. That is not what decides the size. On a site with motors, the set is almost always chosen by the largest motor starting, because the current surge at start drags the voltage down. This one works both out and tells you which is governing.
Results
Worked example
A pumping station: 45 kW of running load at pf 0.8 on 400 V, with a 15 kW pump starting direct on line.
Running demand = 45 / 0.8 = 56.3 kVA
The 15 kW pump draws about 30.1 A at full load, so a 6.5 × direct on line start is roughly 195 A - about135 kVA in one block.
At a 60 % step limit the set has to be at least135 / 0.6 = 226 kVA. That is four times the running demand, and it is the motor start paying for it, not the site.
Start the same pump star-delta and the block drops to about 45 kVA. The set needed falls to roughly 80 kVA - and what now governs is simply the peak while starting, not the step limit. Same site, same pump, a third of the generator.
A first-pass estimate for comparing options, not a specification. Real sizing depends on the alternator's reactance, the order loads are brought on, non-linear loads such as UPS and inverters, and the voltage dip the installation can actually tolerate. Confirm the final selection with the supplier before ordering. Derating figures used here are common rules of thumb and vary between manufacturers.
Standards reference: Duty ratings (ESP, PRP, COP) are defined in ISO 8528-1; transient performance classes in ISO 8528-5. Neither standard is reproduced here - consult the published documents for the definitions and limits.