Exposed Live Conductors / Busbars Inside Consumer Unit
Exposed live copper busbar or terminal screws directly accessible to touch without the use of a key or tool (e.g. missing blanking plate or fractured enclosure lid).
Standardized condition report observation wording and defect classifications aligned with Electrical Safety First Best Practice Guide 4 (BPG4 Issue 5) and BS 7671:2018+A3:2024. Search 40+ scenarios and copy compliant wording directly to your certification software clipboard.
Risk of injury. Immediate remedial action required.
Urgent remedial action required to eliminate risk.
Installation does not comply with latest BS 7671 standard.
Potential safety issue that cannot be verified without delay.
Exposed live copper busbar or terminal screws directly accessible to touch without the use of a key or tool (e.g. missing blanking plate or fractured enclosure lid).
Total absence of an effective earth connection to the installation (main earthing conductor severed, missing, or disconnected from main earthing terminal).
Incoming supply line and neutral reversed, or single-pole switches and protective devices connected in the neutral conductor instead of line.
Cables with severely degraded, crushed, or burned sheath exposing uninsulated live conductors accessible to touch in accessible locations.
Absence of 30mA RCD protection for socket-outlets rated up to 32A that could reasonably be expected to supply portable electrical equipment outdoors (e.g. lawnmowers, pressure washers).
Earth fault loop impedance (Zs) exceeds the maximum permitted in BS 7671 Chapter 41 for the installed overcurrent device, with no supplementary RCD to guarantee disconnection within required time.
Metallic incoming service pipes (gas, water, oil) that are extraneous-conductive-parts enter the premises without main protective bonding conductors connected to the Main Earthing Terminal (MET).
A standard 230V 13A socket-outlet is installed less than 2.5m horizontally from the edge of the bath or shower tray.
Top horizontal surface of consumer unit has unsealed cable entries or gaps larger than 1.0mm diameter, failing to satisfy IP4X / IPXXD.
Overhead or surface-mounted cables supported entirely by plastic trunking or plastic clips without metallic fire-rated fixings, posing premature collapse hazard in a fire.
Type AC RCD installed on circuits supplying equipment known to generate smooth DC leakage or high frequencies (EV chargers, VFD inverters, variable heat pumps), causing magnetic core saturation and failure to trip on AC earth faults.
Class I metal light switches or metallic light luminaires installed on circuits lacking an effective circuit protective conductor (CPC).
Cables concealed in plaster walls at a depth of less than 50mm installed within prescribed safe zones but lacking 30mA RCD additional protection (where no other specific hazard exists).
Absence of required statutory warning labels (e.g. "Safety Electrical Connection - Do Not Remove", Periodic Inspection Notice, or Harmonised Colour Warning Label where mixed colours exist).
Plastic (combustible) consumer unit in domestic premises installed under earlier regulations, showing no thermal damage or loose terminal connections.
Consumer unit lacks a Type 2 Surge Protection Device (SPD) to protect against transient overvoltages of atmospheric origin or switching surges.
Circuit connected to protective device without identification or labeling, disappearing into building fabric where the load and destination cannot be verified during inspection.
Main bonding conductor leaves main earthing terminal but connection to incoming gas/water service cannot be visually located or verified due to boxed-in ductwork or physical obstruction.
RCD trips spontaneously upon connecting test leads or exhibits erratic trip times, indicating borrowed neutrals across separate RCD banks or standing leakage exceeding 9mA.
Cracked or smashed socket-outlet faceplate allowing direct finger contact with 230V live terminals.
Outdoor electric vehicle charging point utilizing supply PME (TN-C-S) earth without an approved open-PEN detection device, independent earth electrode, or isolating transformer.
Solar PV string inverter installed without an adjacent, load-break rated lockable DC isolator on the DC string input conductors.
Circuit protective device rated higher than the derated current-carrying capacity of the cable (e.g. 32A MCB protecting 1.5mm² or 2.5mm² radial cable).
Domestic lighting circuits lacking 30mA RCD protection, installed when RCDs were not mandatory for domestic lighting under earlier 16th/17th edition rules.
Testing reveals an open circuit in the line, neutral, or CPC conductors of a 32A ring final circuit, effectively converting it into two overloaded radial circuits.
Existing main protective bonding conductor to incoming gas or water is 6mm² copper instead of the current 10mm² requirement under BS 7671 Table 54.8 on a PME installation.