REFERENCE // PRINTABLE FIELD CHECKLISTSHSE GS38 • BS 7671:2018+A3 • BS 5266 • BS EN 60204-1
A4 PRINT-OPTIMIZED INSTRUMENTS

Printable Electrical Field Checklists

Standardized engineering inspection and quality control sheets designed for on-site execution. Use on screen or click "šŸ–Øļø Print / Save as PDF" to generate a clean, unbranded, high-contrast A4 hardcopy sheet.

HSE GS38 SAFE ISOLATION VERIFICATION CHECKLIST

Electricity at Work Regulations 1989 (EAWR Regs 12, 13 & 14) • HSE Guidance Note GS38

Permit / Job Ref: ___________________
Date & Time: ___________________
Client / Site Location: ________________________________________________
Equipment / Circuit ID: ________________________________________________
Duty Holder / Authorised Person: ________________________________________
Competent Electrician / Engineer: ____________________________________

10-Step Sequential Verification Procedure

StepCheckRequired Safety Action & Standard ProcedureInitials / Time
1Permission & Consultation: Inform duty holder / occupants of isolation and confirm permission to isolate supply without operational disruption._______________
2Identify Point of Isolation: Verify correct circuit breaker, isolator, switch-fuse or distribution board using verified drawings and labels._______________
3Open Isolator / Switch: Switch the local switch-disconnector or circuit protective device to the open (OFF) position._______________
4Lock Off & Retain Key: Secure the isolator in the OFF position using an approved lockout hasp and unique-key safety padlock. Retain the key on your person._______________
5Attach Warning Notice: Fix a prominent warning tag stating your name, contact phone number, date, and reason for lockout._______________
6Prove Voltage Indicator (Pre-Check): Test an approved 2-pole voltage detector (BS EN 61243-3 / GS38 with ≤ 4mm exposed tips & finger guards) against a known proving unit._______________
7Test All Conductors Dead: Measure between all line conductors, neutral, and protective earth at point of work:
L1–L2 [ ] • L2–L3 [ ] • L3–L1 [ ] • L1–N [ ] • L2–N [ ] • L3–N [ ] • L1–E [ ] • L2–E [ ] • L3–E [ ] • N–E [ ]
_______________
8Re-Prove Voltage Indicator (Post-Check): Immediately re-test the voltage detector against the proving unit to confirm tester remained 100% operational during test._______________
9Check Secondary / Stored Energy Sources: Confirm absence of backfeeds from UPS systems, PV inverters, standby generators, or charged DC capacitors._______________
10Commence Work / Permit Sign-Off: Safe working area established. Conductors proven dead. Safe to commence electrical intervention._______________

Electrician / Inspector Signature:

I confirm that safe isolation has been executed strictly in accordance with EAWR 1989 and HSE GS38.

De-Isolation & Handover Signature:

Lockout padlock removed and installation safely re-energized following successful verification.

MINOR ELECTRICAL INSTALLATION WORKS TEST SCHEDULE

BS 7671:2018+A3:2024 • Part 6 (Inspection and Testing of Minor Additions and Alterations)

Cert Ref: ___________________
Date of Test: ___________________
Client Name: _______________________________________________________
Installation Address: ________________________________________________
Earthing System: [ ] TN-S   [ ] TN-C-S (PME)   [ ] TT
Supply Ze / Ipf: Ze: ________ Ω • Ipf: ________ kA

Section 1: Description of Minor Works & Circuit Parameters

Description of Work:____________________________________________________________________________________
DB Designation / Way: _______________Device Type & Rating: MCB / RCBO Type ____ / ____ ABreaking Capacity: ____ kAConductor CSA: Live: ____ mm² / CPC: ____ mm²

Section 2: On-Site Test Results Schedule

Continuity (Ω)Insulation Resistance (MΩ @ 500V DC)Loop & FaultRCD Operating Characteristics
r1, rn, r2 (Ring)R1 + R2R2 (Wander)Live – LiveLive – EarthNeutral – EarthMeasured Zs (Ω)Trip @ 1× IΔn (ms)Trip @ 5× IΔn (ms)
r1: ____
rn: ____
r2: ____
________ Ω________ Ω________ MΩ________ MΩ________ MΩ________ Ω
(Max: _____ Ω)
________ ms
(Max 300 ms)
________ ms
(Max 40 ms)
Test Instrument Serial #: _______________________________________________
Calibration Expiry Date: ______________________________________________

Declaration of Conformity:

I certify that the minor works detailed above comply with BS 7671:2018+A3:2024 and does not impair existing installation safety.

Inspector Name & Qualification:

Name: ________________________ • Position: ________________________

EMERGENCY LIGHTING 3-HOUR DISCHARGE INSPECTION LOG

BS 5266-1:2016 • BS EN 50172 / BS 5266-8 (Annual Full Duration Test Register)

Log Sheet Ref: ___________________
Inspection Date: ___________________
Building / Premises Name: ____________________________________________
Floor / Area Inspected: ________________________________________________
Responsible Person / Duty Holder: ____________________________________
Testing Engineer / Contractor: _______________________________________

Luminaire Inspection & 3-Hour Discharge Schedule

Unit IDLuminaire Location / RoomType (M/NM)LED Charge1-Hr Check3-Hr CheckPass/FailDefects & Remedial Actions
EL-01___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-02___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-03___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-04___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-05___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-06___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-07___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________
EL-08___________________________M / NM[ ] OK[ ] PASS[ ] PASSP / F___________________________

Engineer Completion Signature:

I confirm that all luminaires above underwent a continuous 3-hour discharge test in compliance with BS 5266.

Premises Handover & Re-charge Verification:

Main normal lighting restored and battery charging circuits operational (allow 24h recharge for full autonomy).

MOTOR & CONTROL PANEL COMMISSIONING & QC SHEET

BS EN 60204-1:2018 (Machinery Electrical Equipment) • BS EN 60034 • PUWER 98

Machine Ref / Tag: ___________________
Commissioning Date: ___________________
Motor Make & Model: ________________________________________________
Rated Power & Voltage: ________ kW • ________ V (Δ / Y)
Full Load Current (FLC): ________ A • Rated RPM: ________
Starting Method: [ ] DOL   [ ] Star-Delta   [ ] Soft-Start   [ ] VFD

Pre-Energization Cold Checks

CheckInspection Item / Testing RequirementMeasurement / ValueStatus
Shaver / Bolt Torque: Foundation bolts, coupling alignment, and terminal box screws torqued.Specified: _______ Nm[ ] PASS
Winding Resistance Balance: Measure phase-to-phase cold resistance balance (U1-U2, V1-V2, W1-W2).U: ____ Ω • V: ____ Ω • W: ____ Ω[ ] PASS
Insulation Resistance (Phase to Earth): Test @ 1000V DC for 1 minute (≥ 200 MΩ required).Measured: ________ MΩ[ ] PASS
Thermal Overload Relay Setting: Dial set to match motor nameplate FLC (or FLC × 0.58 for Star-Delta).Dial Set: ________ A[ ] PASS
Safety Interlocks (BS EN 60204-1 §9.2): E-stop Category 0/1 hardwired trip and anti-restart test.Cat 0 / Cat 1 / STO[ ] PASS

Live Energization Running Tests

CheckLive Running Verification ParameterMeasured ValueStatus
Phase Sequence & Rotation: Confirm shaft rotation matches machine direction arrow.L1 – L2 – L3 [CW / CCW][ ] PASS
Running Currents (Full Load): Measure line current on all 3 phases under operating load.IL1: ____ A • IL2: ____ A • IL3: ____ A[ ] PASS
Bearing Temperature & Vibration: Check for abnormal acoustic noise or excessive heating.Drive end: ____ °C • Non-drive: ____ °C[ ] PASS

Commissioning Engineer:

I verify that this drive train and control panel meet BS EN 60204-1 safety standards.

Production / Plant Manager Sign-off:

Equipment accepted for operational service.

UK ELECTRICAL NEWS